Inspection
Inspection Details
Equipment ID
6365
6365
Inspection Date
7/26/2019
7/26/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Richard Dalman
Richard Dalman
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
20
20
External ID
6568d4e8-bfd5-46c6-854c-b8239ff1e0b1
6568d4e8-bfd5-46c6-854c-b8239ff1e0b1
Location
Corby Building
422 FELIX ST, SAINT JOSEPH, MO
422 FELIX ST, SAINT JOSEPH, MO
Owner
Corby Senior Living
PO BOX 374, PICO RIVERA, CA 90660-0374
PO BOX 374, PICO RIVERA, CA 90660-0374
Billing
Attn: Corby Senior Living
PO BOX 374, PICO RIVERA, CA 90660-0374
PO BOX 374, PICO RIVERA, CA 90660-0374
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Need to post fire service instructions inside the elevator | 12/3/2019 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Need to replace governor rope due to excessive wire breaks and rouging. | 11/3/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need to post emergency evacuation of passengers form inside machine room. | 9/14/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Need to remove nonelevator related material and trash from machine room floor. | 9/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 | Yes | No | Suspension ropes need to be shortened to provide proper runby. | 11/3/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Remount resistor on car controller. Resistor is hanging by electrical wires on resistor. | 7/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 7/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Install seal on machine brake spring tension adjustment nut. | 7/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Remount resistor on controller. Resistor is hanging by electrical wires | 7/16/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 12/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace worn traction sheave liners | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2.5 Rope Tension (Re-Inspect) | Yes | No | Equalize hoist rope tension | 12/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Lobby dial position indicator does not operate and needs to be repaired. | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | Yes | emergency lights not working. | 3/3/2026 |