Equipment ID
7243
7243
Inspection Date
2/21/2018
2/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sheila Swett
Sheila Swett
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
70dn
70dn
Location
Eric P Newman Educational Center
320 S Euclid Ave, St. Louis, MO
Phone: (314) 747-0740
320 S Euclid Ave, St. Louis, MO
Phone: (314) 747-0740
Owner
WUSM
660 S, Euclid, St. Louis, MO 63110
660 S, Euclid, St. Louis, MO 63110
Billing
Attn: WUSM
660 S, Euclid, , MO 63110
660 S, Euclid, , MO 63110
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Demarcation lights are not working. | 4/14/2020 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 805.7 | No | No | Demarcation lighting out - top and bottom. | 4/14/2020 |
| A17.1-2016 : Elevators | 7.7 - Combplate and comb step impact device | 8.6.8.4 | No | No | Combplate impact device (vertical switch) not working at top landing. | |
| A17.1-2016 : Elevators | 7.7 - Combplate and comb step impact device | 8.11.4.1(g) | No | No | Combplate tooth broken at top landing. | |
| A17.1-2016 : Elevators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3.3 | No | No | Step/skirt performance index over maximum allowable. | |
| A17.1-2016 : Elevators | 7.7 - Combplate and comb step impact device | 8.6.8.4 | No | No | Combplate impact device setting (vertical plane) at top landing of escalator over allowable limit. | |
| A17.1-2016 : Elevators | 7.7 - Combplate and comb step impact device | 8.6.8.4 | No | No | Combplate impact device (vertical switch) not working at top landing. | |
| A17.1-2016 : Elevators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3.3 | No | No | Step/skirt performance index over maximum allowable. | |
| A17.1-1996 : Escalators | 7.5 - Lighting | 805.7 | No | No | Demarcation lighting not working (both top and bottom). | |
| A17.1-1996 : Escalators | 7.1 - General fire protection | 801 | No | No | Observed opening in deck. Exterior deck plates sliding down, creating opening. | |
| A17.1-2016 : Elevators | 7.7 - Combplate and comb step impact device | 8.6.8.4 | No | No | Combplate impact device (vertical switch) not working at top landing. | |
| A17.1-2016 : Elevators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3.3 | No | No | Step/skirt performance index over maximum allowable. | |
| A17.1-1996 : Escalators | 7.5 - Lighting | 805.7 | No | No | Demarcation lighting not working (both top and bottom). | |
| A17.1-2016 : Elevators | 7.3 - Handrails | 8.6.8.1 | No | No | Handrails cracking, presenting pinch points. Both handrails. |