Inspection
Inspection Details
Equipment ID
24536
24536
Inspection Date
7/17/2019
7/17/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
John Oldham
John Oldham
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
8d317187-9424-4998-8de0-752b5b5ffe8c
8d317187-9424-4998-8de0-752b5b5ffe8c
Location
Steelcote Lofts
801 Edwin Street, St. Louis, MO
Phone: (314) 616-2196
Email: chris@pinnaclecontracting.com
801 Edwin Street, St. Louis, MO
Phone: (314) 616-2196
Email: chris@pinnaclecontracting.com
Owner
Attn: Chris Anderson
Steelcote Lofts, LLC
8040 Teasdale Ave, St. Louis, MO 63130
Phone: (314) 616-2196
Email: chris@pinnaclecontracting.com
Steelcote Lofts, LLC
8040 Teasdale Ave, St. Louis, MO 63130
Phone: (314) 616-2196
Email: chris@pinnaclecontracting.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | x | Provide 19 ft at the floor level in front of control on top floor. | 7/17/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.5 | x | Bevel all ledges at 4" or greater. | 7/17/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.1 | x | Seal all hoistway penetration. | 7/17/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | x | Glass in rear hoistway wall shall be laminated ANSI Z97 rated and etched. | 7/17/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.26.2.7 | x | Sump pump shall be 3000 GPM or larger and not tied directly to the sewer. | 7/17/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | x | Install ABC fire extinguisher on car top. | 7/17/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.5 | x | Hoistway signage shall be permanent and read ELEVATOR HOISTWAY. | 7/17/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No current maintenance records on site. | 9/29/2020 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No current operating certificate on display. | 9/29/2020 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | x | Car door restrictor does not work. | 6/24/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | x | Car door restrictor does not work. Repair or replace 8.6.4.13.1 (l) | 9/12/2023 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Need to clean pit to remove debris, water and /or oil and address sources | 2/28/2024 | ||
A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | x | Car door restrictor does not work, needs repaired. Re-inspection required | 7/29/2024 |