Inspection
Inspection Details
Equipment ID
7694
7694
Inspection Date
2/21/2018
2/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Relief Valve Pressure
440
440
Slide
NA
NA
Governor Rope Pull
7694
7694
Door Closing Force
Lobby
Lobby
External ID
7694
7694
Location
Mercy Seat Apartments
4452 Washington Blvd, St. Louis, MO
Phone: (314) 652-6555
4452 Washington Blvd, St. Louis, MO
Phone: (314) 652-6555
Owner
St. Andrews Management Services Inc
9600 Halls Ferry Rd, Jennings, MO 63136
9600 Halls Ferry Rd, Jennings, MO 63136
Billing
Attn: St. Andrews of Jennings
9600 Halls Ferry Rd, , MO 63136
9600 Halls Ferry Rd, , MO 63136
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Repair Phase 2 Fire Services | 1/28/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Door close button not working on fire service | 4/26/2019 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | A heat detectors shall be installed in the machine room and top of hoistway within 2' of each sprinkler head. | 7/9/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | A shunt trip disconnect shall be installed. | 7/9/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need Maintenance control program on site and posted on controller | 9/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency phone not working no power in controller to phone line | 8/26/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need maintenance control program on site | 9/25/2020 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 1001.2(b)(4) | No | No | Replace missing section of machine room ceiling | 6/29/2021 |
| A17.1-2016 : Elevators | 1.7 - Car door or gate | 2.13.2.1 | No | No | Repair car door closure on 1st floor hatch door | 4/22/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM | 4/10/2025 |
| A17.1-2016 : Elevators | 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) | 8.6.11.1 Firefighters’ Emergency Operation | No | No | PERFORM MONTHLY FIRE SERVICE TEST AND DOCUMENT ON THE LOG POSTED IN THE MACHINE ROOM | 4/10/2025 |