Inspection
Inspection Details
Equipment ID
8526
8526
Inspection Date
7/16/2019
7/16/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
Na
Na
Door Closing Force
18
18
External ID
8068a601-e800-4a88-9127-3f91bd81a284
8068a601-e800-4a88-9127-3f91bd81a284
Location
Manchester 270 Office Center
12444 POWERSCOURT DR, SAINT LOUIS, MO
12444 POWERSCOURT DR, SAINT LOUIS, MO
Owner
Eckelkamp Inc
12444 POWERSCOURT DR STE 150, SAINT LOUIS, MO 63131-3671
12444 POWERSCOURT DR STE 150, SAINT LOUIS, MO 63131-3671
Billing
Attn: Eckelkamp Inc
12444 POWERSCOURT DR STE 150, SAINT LOUIS, MO 63131-3671
12444 POWERSCOURT DR STE 150, SAINT LOUIS, MO 63131-3671
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace seals on traction driving machine, leaking fluid. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each elevator | |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)8 | Yes | Yes | Test car safeties with rated load at rated speed. Red tagged, Re-inspection required | 9/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | Yes | Traction driving machine will not pick rated load due to suspension ropes loosing traction on machine sheave. Red tagged, removed from service. Re-inspection required | 9/28/2022 |
| MO Minimum : Elevators | (D) - Brakes | (D)1 | Yes | Yes | Traction machine brake hub is off center causing vibration and brake to overheat, need to replace brake. Red-tagged, removed from service. Re-inspection required | 10/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each unit. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | Re-inspection of drive machine brake, unit will not run (keeps tripping overload) Could not test brake, elevator still Red-tagged, Re-inspection required | 10/12/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Hoist ropes shall be shortened, the counterweight is touching the springs when the car is at the top floor. Re-inspection required within 30 days | 9/1/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room |