Inspection
Inspection Details
Equipment ID
11013
11013
Inspection Date
7/19/2019
7/19/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Leo
David Leo
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
306c0ecb-e31c-4017-9a93-484ee200690a
306c0ecb-e31c-4017-9a93-484ee200690a
Location
Meridian Garage II
8352 MUSICK MEMORIAL DR, BRENTWOOD, MO
8352 MUSICK MEMORIAL DR, BRENTWOOD, MO
Owner
DCM Group
8300 EAGER RD STE 601, BRENTWOOD, MO 63144-1419
8300 EAGER RD STE 601, BRENTWOOD, MO 63144-1419
Billing
Attn: DCM Group
8300 EAGER RD STE 601, BRENTWOOD, MO 63144-1419
8300 EAGER RD STE 601, BRENTWOOD, MO 63144-1419
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | No pit lighting. | 8/17/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. Note: The posted certificate is expired. | 11/8/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. Note: A fire testing log has been included in the MCP, but has not entries. | 11/8/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The emergency/standby power shall be tested. Note: Building management in scheduling this for after hours. | 9/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Fire service operation shall be tested as required. Note: Building management in scheduling this for after hours. | 9/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. Note: The hoistway door safety retainers are missing from the bottom of the door panel and shall be installed. | 9/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | This test is incomplete. The hoistway was run, alarm bell, emergency lights, door torque were tested. All other work needs to be completed. Weights were not present during the inspection. Category 5 testing still needs to be completed. | 9/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The emergency/standby power shall be tested. Note: Building management in scheduling this for after hours. Reinspection Violation still remains after 9/21/2023 inspection. | 11/3/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Fire service operation shall be tested as required. Note: Building management in scheduling this for after hours. Reinspection Violation still remains after 9/21/2023 inspection. | 11/3/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. Note: The hoistway door safety retainers are missing from the bottom of the door panel and shall be installed. Reinspection Violation still remains after 9/21/2023 inspection. | 11/3/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | The top and bottom of horizontally sliding doors shall be provided with a means of retaining the closed door panel in position if the primary guiding means fail. Note: The hoistway door safety retainers are missing from the bottom of the door panel and shall be installed. Reinspection Violation still remains after 11/3/2023 inspection. | 11/30/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.4 Car top light and Outlet | No | No | Car top light/light switch does not work. | 8/2/2024 |