Inspection
Inspection Details
Equipment ID
9041
9041
Inspection Date
7/19/2019
7/19/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
600
600
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
8eb508fb-9d2d-4957-b55e-06c54d69fa9c
8eb508fb-9d2d-4957-b55e-06c54d69fa9c
Location
Vatterott College-Sunset Hills Campus
12900 MAURER INDUSTRIAL DR, SAINT LOUIS, MO
12900 MAURER INDUSTRIAL DR, SAINT LOUIS, MO
Owner
Sol Spaces LLC
12970 MAURER INDUSTRIAL DR STE 200, SAINT LOUIS, MO 63127-1542
12970 MAURER INDUSTRIAL DR STE 200, SAINT LOUIS, MO 63127-1542
Billing
Attn: Sol Spaces LLC
12970 MAURER INDUSTRIAL DR STE 200, SAINT LOUIS, MO 63127-1542
12970 MAURER INDUSTRIAL DR STE 200, SAINT LOUIS, MO 63127-1542
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 8/8/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 8/26/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be operational. | 11/22/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not work with 110 VAC off. | 11/22/2024 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light does not work with 110 VAC off. | 11/22/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | The pit shall be kept clean. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve that is not sealed. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | Yes | Emergency phone shall be operational. Note: Violation from 2022 still not corrected. Elevator Red Tagged. | 1/22/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | Yes | Emergency bell does not work with 110 VAC off. Note: Violation from 2022 still not corrected. Elevator Red Tagged. | 1/22/2025 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | Yes | Emergency light does not work with 110 VAC off. Note: Violation from 2022 still not corrected. Elevator Red Tagged. | 1/22/2025 |