|
conversion
|
conversion
|
conversion - reinspect
|
Yes
|
No
|
The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required.
|
8/23/2018
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.2 - Stop switches
|
2.26.2.21
|
No
|
No
|
The emergency stop switch inside the elevator fireman’s service panel is overridden when fireman’s service phase I is activated. This stop switch shall remain operable at all times in this panel.
|
8/18/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
No
|
No
|
The elevator pit shall be cleaned of dust and debris.
|
8/18/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
No
|
No
|
The sump pump covers in pit are not in place as required. Locate missing sump pump covers and install them as required.
|
8/18/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13
|
No
|
No
|
The hoistway door interlock cover was missing on the 2nd landing, replace missing interlock cover.
|
10/6/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
Yes
|
No
|
The emergency car lighting is not operational.The fixture shall be repaired to operate. Reinspection required.
|
1/31/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
No
|
No
|
The pit light fixtures failed to illuminate in the pit. Repair pit light fixtures to provide lighting of not less than five (5) foot candles at the pit floor for maintenance and emergency personnel.
|
10/6/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The elevator ADA telephone inside the elevator is not operating correctly. Check and repair this phone for proper operation and passenger safety. Reinspection required.
|
8/2/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
No
|
No
|
The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
|
|