Inspection
Inspection Details
Equipment ID
8921
8921
Inspection Date
7/29/2019
7/29/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Terhune
Michael Terhune
Mechanic Name
Jason Hernke
Jason Hernke
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
a3d63d07-958b-4711-a7fd-06a5c85ddab9
a3d63d07-958b-4711-a7fd-06a5c85ddab9
Location
Woodrail
NIFONG & FORUM, COLUMBIA, MO
NIFONG & FORUM, COLUMBIA, MO
Owner
Attn: University of Missouri Healthcare
University of Missouri Healthcare
1 HOSPITAL DR, COLUMBIA, MO 65212
Phone: (000) 000-0000
Email: ditzfeldjs@health.missouri.edu
University of Missouri Healthcare
1 HOSPITAL DR, COLUMBIA, MO 65212
Phone: (000) 000-0000
Email: ditzfeldjs@health.missouri.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 1/25/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Provide a sump hole cover per 40-05.065 | 1/25/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide machine room lighting of not less than 10ft candles measured at the floor through out the entire machine room | 1/25/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Need elevator prints on site | 12/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Excessive leaking during 15b minute set. Repair/replace control valve | 12/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need code dat plate conforming to sec 8.9 | 12/14/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Place current state certificate in machine room | 12/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Excessive leaking during 15b minute set. Repair/replace control valve | 12/22/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Need to install non combustible sump hole cover, flush with pit floor | 1/14/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting in machine room shall be a minimum of 10 foot candles to floor | 9/9/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to install a non-combustible sump hole cover flush with pit floor | 1/14/2025 |