Inspection
Inspection Details
Equipment ID
8323
8323
Inspection Date
7/25/2019
7/25/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
Na
Na
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
5301a9a8-1ef8-4136-ab32-4083ca8bd116
5301a9a8-1ef8-4136-ab32-4083ca8bd116
Location
Cordell Bldg
11737 ADMINISTRATION DR, SAINT LOUIS, MO
11737 ADMINISTRATION DR, SAINT LOUIS, MO
Owner
Cordell Group LLC
11737 ADMINISTRATION DR, SAINT LOUIS, MO 63146-3413
11737 ADMINISTRATION DR, SAINT LOUIS, MO 63146-3413
Billing
Attn: Cozad Property Management
16 SUNNEN DR, SAINT LOUIS, MO 63143-3823
16 SUNNEN DR, SAINT LOUIS, MO 63143-3823
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.8 - Top emergency exit | 8.11.2.1.3(l) | No | No | Exit should be tool-less fastener. | 7/25/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | Emergency light needs to work. | 7/25/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell needs to work. | 7/25/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed. Perform test on or before next annual inspection. | 4/15/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Building under construction. Fire panel non-operational. Unable to lift wire to simulate smokes. Observed fire service modules hanging by wires above machine room door. Install per code. | 4/14/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | Machine room door is not self-locking. | 4/15/2021 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | All lobby entrances are missing braille/tactile plates. | 4/15/2021 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | All lobby entrances missing Braille/tactile places. Replace | 4/26/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed. Perform OSV test on or before next annual inspection. | 4/26/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Emergency backup generator testing needs to be performed. Re-inspection required | 3/31/2026 |