Inspection
Inspection Details
Equipment ID
8519
8519
Inspection Date
8/1/2019
8/1/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Robert Kehm
Robert Kehm
Relief Valve Pressure
Slide
18 1/2
18 1/2
Governor Rope Pull
50/560
50/560
Door Closing Force
23
23
External ID
975b20e1-6cbb-466d-bd70-cdd137b1b396
975b20e1-6cbb-466d-bd70-cdd137b1b396
Location
Business Bank Tower
8000 MARYLAND AVE, CLAYTON, MO
Phone: (314) 000-0000
8000 MARYLAND AVE, CLAYTON, MO
Phone: (314) 000-0000
Owner
Attn: UNK
Hoffmann International Commercial Real Estate
8000 MARYLAND AVE, CLAYTON, MO 63105
Phone: (314) 725-8333
Email: jsorrentino@hoffmanncre.com
Hoffmann International Commercial Real Estate
8000 MARYLAND AVE, CLAYTON, MO 63105
Phone: (314) 725-8333
Email: jsorrentino@hoffmanncre.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Compensating chains needs to be shortened. | 6/12/2019 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Need to perform brake, buffer, car & counterweight, safety slide testing. | 8/1/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | The MCP is missing the evacuation procedures. (This item is for notification purposes for future violation in 2022) | 7/30/2021 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Red tag issued: damaged hoistway ropes. Replace ropes and check driver for damaged grooves. | 9/5/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service operation shall be tested. | 9/5/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current Mo state operating certificate ahll be posted in the elevator equipment room in a noncombustible frame with a clear protective vision place over it. | 12/22/2025 |
| A17.1-2016 : Elevators | 3.2 - Car top light and outlet | 8.10.2.2.3(b) | No | No | The car top light shall be operational | 12/22/2025 |
| A17.1-2016 : Elevators | 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) | 8.6.11.1 Firefighters’ Emergency Operation | No | No | Firefighters phase one instructions shall be posted near the phase one keyswitch in the hallway at the egress floor. | 12/22/2025 |
| A17.1-2016 : Elevators | 3.2 - Car top light and outlet | 8.10.2.2.3(b) | No | No | The electrical fitting on the car-top emergency exit switch is broken and shall be repaired or replaced. | 12/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Suspension ropes shall be shortened. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room floors, machinery, and control spaces shall be kept free of water, dirt, rubbish, oil, and grease. |