Inspection
Inspection Details
Equipment ID
15187
15187
Inspection Date
7/31/2019
7/31/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
560
560
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
6a94475f-10d4-49ca-a029-daaa4dcdfdb5
6a94475f-10d4-49ca-a029-daaa4dcdfdb5
Location
St. Charles West High School
3601 DROSTE RD, SAINT CHARLES, MO
3601 DROSTE RD, SAINT CHARLES, MO
Owner
School District of the City of St. Charles
400 N 6TH ST, SAINT CHARLES, MO 63301-1838
400 N 6TH ST, SAINT CHARLES, MO 63301-1838
Billing
Attn: City of St. Charles School District
400 N 6TH ST, SAINT CHARLES, MO 63301-1838
400 N 6TH ST, SAINT CHARLES, MO 63301-1838
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.1.7 | Yes | No | 8.6.1.7.5 - The emergency lowering device (ERU) shall be operational. | 11/5/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/18/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/18/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 8/18/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. The posted certificate is expired. | 10/10/2024 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. The tag is expired. | 10/10/2024 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | In electrical equipment rooms, the illumination shall not be controlled by automatic means only. The lights are controlled by a motion sensor in the womens' locker room outside of the machine room. | 10/10/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering not interfaced with disconnect. Repair connect and test. | 7/24/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 7/24/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/31/2025 |