MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
Yes
|
No
|
The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The emergency stop switch was not rendered inoperative in the car when phase I was activated.
|
8/8/2019
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
No
|
No
|
There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri.
|
7/29/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
No
|
No
|
The elevator machine room roof is leaking noticeably and shall be repaired.
|
7/29/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
The testing has not been completed on the elevator at this time. The fire service and emergency power testing shall be performed before the inspection is completed.
|
6/11/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
The testing has not been completed on the elevator at this time. The fire service and emergency power testing shall be performed before the inspection is completed. Re-inspection required
|
7/29/2026
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
When the elevator was tested on emergency power jewel, the elevator shut down and would not run, needs repaired. Re-inspection required
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
No
|
No
|
Up to date maintenance records shall be kept on site for each elevator.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
No
|
No
|
The elevator machine room roof is leaking noticeably and shall be repaired.
|
|