Inspection
Inspection Details
Equipment ID
14907
14907
Inspection Date
8/12/2019
8/12/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
510
510
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
ba239039-59f4-4a28-a6ee-4b138db286e5
ba239039-59f4-4a28-a6ee-4b138db286e5
Location
Courtyard by Marriott
11888 WESTLINE INDUSTRIAL DR, SAINT LOUIS, MO
Phone: (314) 997-1200
11888 WESTLINE INDUSTRIAL DR, SAINT LOUIS, MO
Phone: (314) 997-1200
Owner
Courtyard by Marriott
11888 WESTLINE INDUSTRIAL DR, SAINT LOUIS, MO 63146-3313
11888 WESTLINE INDUSTRIAL DR, SAINT LOUIS, MO 63146-3313
Billing
Attn: Courtyard by Marriott
11888 WESTLINE INDUSTRIAL DR, SAINT LOUIS, MO 63146-3313
11888 WESTLINE INDUSTRIAL DR, SAINT LOUIS, MO 63146-3313
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 8/12/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | Door restrictor not working. | 8/12/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 10/28/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger pump system from the pit and provide code compliant means of oil collection. | 9/6/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Ground water entering machine room. Clean and provide means of correction. | 9/6/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Provide emergency phones with correct car numbering. | 11/4/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide written maintenance control program on site. | 9/6/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. | 9/6/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current certificate. | 9/6/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Battery backup lowering unit not working correctly. | 11/2/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | There is no state operating certificate in the machine room. | 11/14/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Failed Cat 1 standby power test. Re-inspection required | 9/12/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | Machine room air conditioner is not working properly, replace or repair as needed. | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Sump hole full of oil, remove. Determine if the sump pump still works, if not then replace. | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean the car top. | 12/9/2025 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | OSV in the pit is due for testing, provide. | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Sump hole full of oil, remove. Determine if the sump pump still works, if not then replace. | 1/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | Machine room air conditioner is not working properly, replace or repair as needed. | 1/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean the car top. | 1/6/2026 |