Inspection
Inspection Details
Equipment ID
9769
9769
Inspection Date
8/1/2019
8/1/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
51"
51"
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
67d64258-269e-4946-9bd2-ce751246ea97
67d64258-269e-4946-9bd2-ce751246ea97
Location
Bank of America Tower
100 N BROADWAY, SAINT LOUIS, MO
Phone: (314) 421-0640
100 N BROADWAY, SAINT LOUIS, MO
Phone: (314) 421-0640
Owner
Attn: Hertz Investment Group
Hertz Investment Group
100 N BROADWAY STE 300, SAINT LOUIS, MO 63102
Phone: (314) 421-0640
Email: tsullivan@svncompassrock.com
Hertz Investment Group
100 N BROADWAY STE 300, SAINT LOUIS, MO 63102
Phone: (314) 421-0640
Email: tsullivan@svncompassrock.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Emergency bell shall work | 5/23/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | No | No | Need to test fireman's recall. | 11/13/2019 |
| A17.1-1996 : Elevators | 2.17 - Drive machine brake | 1002.3d | Yes | No | Need to do 125% load test. | 8/1/2019 |
| A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 1001.2(e)10 | Yes | No | Need to test car safeties. | 8/1/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emergency lights shall work. | 2/24/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | No | No | Need to test fireman's recall. | 11/13/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emergency lights shall work. | 2/24/2020 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | Replace hoist ropes - two are stretched to maximum limit. | 2/24/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Repair pit lights that are out. | 2/24/2020 |
| A17.1-1996 : Elevators | 5.10 - Compensating chains, ropes, and sheaves | 1001.2(e)(8) | Yes | No | Shorten compensating ropes. | 1/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light does not work, needs repaired. Re-inspection required | 3/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Need to repair the car door restrictor to work. Re-inspection required | 3/14/2025 |