Inspection
Inspection Details
Equipment ID
9155
9155
Inspection Date
7/29/2019
7/29/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Relief Valve Pressure
300
300
Slide
Governor Rope Pull
Door Closing Force
17/15
17/15
External ID
fff0a76a-2399-49a1-b648-145b9ccb1e31
fff0a76a-2399-49a1-b648-145b9ccb1e31
Location
Delhaven Manor
5460 DELMAR BLVD, SAINT LOUIS, MO
Phone: (314) 361-2902
5460 DELMAR BLVD, SAINT LOUIS, MO
Phone: (314) 361-2902
Owner
Delhaven Manor
5460 DELMAR BLVD, SAINT LOUIS, MO 63112-3104
5460 DELMAR BLVD, SAINT LOUIS, MO 63112-3104
Billing
Attn: Delhaven Manor
5460 DELMAR BLVD, SAINT LOUIS, MO 63112-3104
5460 DELMAR BLVD, SAINT LOUIS, MO 63112-3104
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | x | x | Fireman's stop switch shall work. Reinspect only. Unit was not red-tagged. | 11/1/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Repair inoperative emergency phone. | 7/29/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide maintenance control program and updated monthly elevator fire log. | 3/12/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | Provide code compliant machine room lighting (19fc) | 3/12/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 8.11.2.1.2(k) | Provide feeder location for main line and 110v disconnect. | 3/12/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Provide testing of existing emergency battery back-up unit. Written testing procedures are required for maintenance control program. | 9/1/2020 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working, phone line not working. Re-inspection required | 6/8/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | Emergency light shall be operational. | 3/27/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency alarm bell shall be operational. | 3/27/2024 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | x | This elevator is equipped with an overspeed valve and category 5 testing is due. | 3/27/2024 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | x | Doors do not automatically open when battery power is activated. Door operators must be manually reset any time power is lost. | 1/22/2026 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | x | x | The opening of doors shall be on continuous pressure. When pressure is released, doors fail to return to the closed position. | 1/22/2026 |