Inspection
Inspection Details
Equipment ID
24547
24547
Inspection Date
7/31/2019
7/31/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
David Leo
David Leo
Mechanic Name
John Oldham
John Oldham
Relief Valve Pressure
Slide
5
5
Governor Rope Pull
23/120
23/120
Door Closing Force
19
19
External ID
382555f5-7396-432b-b00c-12589c512242
382555f5-7396-432b-b00c-12589c512242
Location
4340A Duncan Avenue
4340 Duncan Ave, St. Louis, MO
Phone: (314) 295-1846
Email: clcolley@tarltoncorp.com
4340 Duncan Ave, St. Louis, MO
Phone: (314) 295-1846
Email: clcolley@tarltoncorp.com
Owner
Attn: Curtis L. Colley
BOBB, LLC
700 Rosedale Ave, St. Louis, MO 63112
Phone: (314) 295-1846
Email: clcolley@tarltoncorp.com
BOBB, LLC
700 Rosedale Ave, St. Louis, MO 63112
Phone: (314) 295-1846
Email: clcolley@tarltoncorp.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Close hoistway penetration | 7/31/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | Yes | No | Increase illumination to 19 ft candles | 7/31/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.5 | Yes | No | Grout floor sills | 7/31/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.13.3.4 | Yes | Yes | Reprogram basement, 3rd & 4th floor smoke detectors to recall to primary floor. | 7/31/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.13.3.4 | Yes | Yes | Reprogram top of hoistway smoke detector to recall to primary floor and flash the hat. | 7/31/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.13.5 | Yes | Yes | Reprogram the top of hoistway heat detector to trip the shunt. | 7/31/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | Yes | No | Pit lights are inoperative. | 7/31/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.26.2.7 | Yes | No | Cover pit sump even with pit floor. | 7/31/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written maintenance control program shall be provided on site for each elevator. | 5/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Door restrictor inoperable, repair in 15 days. Re-inspection required | 8/11/2023 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | Car door restrictor still does not work, parts missing. Re-inspection required | 8/11/2023 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | Car door restrictor is not working. Re-inspection required | 2/6/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 5/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | No | No | Post Phase I instructions near f/f switch in lobby. | 5/27/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | 5/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters' Emergency Operation: Operating Procedures | No | No | Post Phase I instructions near f/f switch in the lobby. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work. |