Inspection
Inspection Details
Equipment ID
9163
9163
Inspection Date
7/16/2019
7/16/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
27
27
External ID
a31d13a2-75f4-4532-99f2-80cb7a3f3b28
a31d13a2-75f4-4532-99f2-80cb7a3f3b28
Location
Westland Place
14515 N OUTER 40 RD, CHESTERFIELD, MO
Phone: (314) 542-0777
14515 N OUTER 40 RD, CHESTERFIELD, MO
Phone: (314) 542-0777
Owner
Attn: Tina Moser
Scott Properties
1065 EXECUTIVE PARKWAY DR STE 300, CREVE COEUR, MO 63141
Phone: (314) 542-0777
Email: tmoser@scottproperties.com
Scott Properties
1065 EXECUTIVE PARKWAY DR STE 300, CREVE COEUR, MO 63141
Phone: (314) 542-0777
Email: tmoser@scottproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | All pits shall be kept dry, clean and free of equipment and materials not relating to the operation of the elevator. | 11/7/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Emergency light shall work. | 11/7/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 10/7/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 7/27/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 10/5/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 10/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 10/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Install a code data plate. It shall read: Missouri Minimums. | 10/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 10/5/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. Note: The log isn't being filled out monthly. | 10/1/2024 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | No | In the case where the car travels above the top landing past the normal directional limit, the up final limit shall be actuated causing power to the pump motor to be interrupted before the car reaches the stop ring. Note: This car is equipped with an up final limit and it shall be operational. Presently the car reaches the stop ring without opening (actuating) the up final limit. The up runby is 5 1/2". | 10/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | The presence of an overspeed valve has been confirmed, along with an installation date of 1984. The overspeed valve shall be scheduled for a category 5 test in 2024. | 10/1/2024 |