Inspection
Inspection Details
Equipment ID
18701
18701
Inspection Date
6/20/2019
6/20/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Vincent Daus
Vincent Daus
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
820
820
Slide
1"
1"
Governor Rope Pull
90/250
90/250
Door Closing Force
20
20
External ID
86a2a63b-5621-4a13-97a7-69e8fb3f64a6
86a2a63b-5621-4a13-97a7-69e8fb3f64a6
Location
Trinity Park Apartment
11019 MOLLERUS DR, SAINT LOUIS, MO
Phone: (314) 868-4300
11019 MOLLERUS DR, SAINT LOUIS, MO
Phone: (314) 868-4300
Owner
Trinity Park Apartments
11043 MOLLERUS DR, SAINT LOUIS, MO 63138-3977
11043 MOLLERUS DR, SAINT LOUIS, MO 63138-3977
Billing
Attn: Trinity Park Apartments
11043 MOLLERUS DR, SAINT LOUIS, MO 63138-3977
11043 MOLLERUS DR, SAINT LOUIS, MO 63138-3977
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | No | No | The machine room door shall be self-closing and self-locking. | 10/25/2019 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | The machine room lighting shall work. | 10/25/2019 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | The machine room shall be cleaned of dirt and debris. | 10/25/2019 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | A rope data tag is required on the hoist ropes. | 10/25/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit light shall work. | 10/25/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | No | No | A fire service testing log shall be kept on-site. | 10/25/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A maintenance log shall be kept on-site. | 10/25/2019 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | No | The hoist ropes are rouging and have crown breaks and require replacement. | 10/25/2019 |
| A17.1-1996 : Elevators | 2.34 - Flexible Hydraulic Hose and Fitting Assemblies | 1004.2(b)(17) | No | No | The high pressure hose is expired. If the unit is equipped with a rupture valve the hose does not need replacing, if no rupture valve is present the high pressure hose shall be replaced. | 2/22/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 10/8/2020 |
| A17.1-1996 : Elevators | 1.2 - Stop switches | 1001.2(a)(2) | No | No | The in car stop switch does not stop the elevator. Repair or replace the switch for proper operation. | 2/24/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 2/23/2021 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV is not sealed. Perform test, tag, and seal upon completion. | 7/27/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/11/2023 |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 204.7 | No | No | Top of hoistway light shall be operational. | 7/11/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Hydraulic pipe in pit is rusted. Take corrective action as needed. |