Inspection
Inspection Details
Equipment ID
10939
10939
Inspection Date
3/21/2018
3/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Relief Valve Pressure
Slide
11"
11"
Governor Rope Pull
90/520
90/520
Door Closing Force
26
26
External ID
Location
St. Louis Police Department
1200 Clark Ave, St. Louis, MO
Phone: (314) 444-5521
1200 Clark Ave, St. Louis, MO
Phone: (314) 444-5521
Owner
St. Louis City of- Police Dept
1200 Clark, St. Louis, MO 63103
1200 Clark, St. Louis, MO 63103
Billing
Attn: St. Louis Metro Police Dept Bldgs Division
1200 Clark Ave, , MO 63103
1200 Clark Ave, , MO 63103
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Machine room roof leaks and drips on elevator equipment. The roof leak shall be repaired. | 4/22/2019 | ||
A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | All lighting in the machine room shall be operational. | 5/21/2020 | ||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | A current tested ABC type fire extinguisher shall be provided in the elevator machine room. Current extinguisher is expired. | 5/21/2020 | ||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | |||
A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | The controller air conditioning shall be operational. | |||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 5/13/2022 | |
A17.1-1996 : Elevators | 2.4 - Machine space | 1001.2(b)(4) | The elevator machine room shall be protected from the weather. (Note: Windows are being left open, and the equipment and machine room floor are showing signs that they have been wet, possibly from a leaky roof). | |||
A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | The car identification number shall be painted on, engraved, or securely attached to the car operating panel and shall be a minimum of 1/2" in height. (Note: The COP currently doesn't have an identification number and is required since this car shares a machine room with cars 1 & 2). | |||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | 2-way communication device shall work, with and without main power, and give proper location. | 10/26/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Suspension rope tail ends shall be properly seized/banded and retaining clips shall be set at proper distance. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Replace missing hoistway door guides. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Reinstall controller AC Cover | |||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Testing incomplete due to unit shutting down during inspection. Weight portions of test at 125%, 100% safeties, slide, and 100% car buffer remaining. | 10/26/2023 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Testing incomplete. Elevator shutdown during testing. Need to test: Emergency light, alarm, and phone. | 12/5/2024 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current state operating permit shall be obtained and displayed in the equipment room. | |||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | MCP fire service testing must be properly documented monthly on log sheet. | |||
A17.1-1996 : Elevators | 3.12 - Pipes, wiring, and ducts | 102 | Pit 4x4 electrical box is missing cover. Exposed wiring. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Repair loose pickup assembly on 1st floor door. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x | x | 2-way communication device still not working. The building is vacant, therefore the elevator is red tagged. |