Inspection
Inspection Details
Equipment ID
24503
24503
Inspection Date
8/6/2019
8/6/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Steven Perez
Steven Perez
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
2180bbbb-e036-4032-9be7-d889a444d841
2180bbbb-e036-4032-9be7-d889a444d841
Location
Ameristar Casinos St. Charles
One Ameristar Blvd, Saint Charles, MO
Phone: (314) 705-7907
Email: dfdriscoll@paric.com
One Ameristar Blvd, Saint Charles, MO
Phone: (314) 705-7907
Email: dfdriscoll@paric.com
Owner
Attn: David Driscoll
Pinnacle Entertainment
8918 Spanish Ridge Ave, Las Vegas, NV 89148
Phone: (314) 705-7907
Email: dfdriscoll@paric.com
Pinnacle Entertainment
8918 Spanish Ridge Ave, Las Vegas, NV 89148
Phone: (314) 705-7907
Email: dfdriscoll@paric.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.1 - General fire protection | 6.1.1 | Yes | No | All construction around escalator shall be completed. | 8/6/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.4 - Entrance and egress ends | 6.1.3.6 | Yes | No | Finish upper landing floor. | 8/6/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.5 - Lighting | 6.1.7.2 | Yes | No | Lighting at lower level deck plate may be below 5 ft candles at night. | 8/6/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.14 - Code data plate | 8.9 | No | No | Post installation code data tag on unit. | 11/3/2020 |
| A17.1-2016 : Elevators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3.3 | Yes | No | Provide skirt index testing, record results. | 3/9/2023 |
| A17.1-2016 : Elevators | 7.7 - Combplate and comb step impact device | 8.6.8.4 | Yes | No | Provide comb impact test. | 3/9/2023 |
| A17.1-2016 : Elevators | 7.3 - Handrails | 8.6.8.15.13 | No | No | Observed cracks in hand rail, right side. | 8/2/2023 |
| A17.1-2016 : Elevators | 8.4 - Drive machine and brake | 8.6.8.15.4 | Yes | No | Provide torque testing of unit brake. | 3/9/2023 |
| A17.1-2016 : Elevators | 8.1 - Machinery space access, lighting, receptacle, and condition | 8.6.8.15.1 | No | No | Provide clean down of the unit. | 3/26/2024 |
| A17.1-2016 : Elevators | 7.19 - Maintenance records | 8.6.1.2.1(a) | No | No | Provide MCP. | 3/26/2024 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 3/26/2024 |
| A17.1-2016 : Elevators | 7.3 - Handrails | 8.6.8.15.13 | No | No | Observed cracks in hand rail, right side. Replace handrail required. | 3/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 6.1.3.3.9 Step/Skirt Performance Index | Yes | No | Need index print out to complete inspection. Re-inspection required | 3/13/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection incomplete, need to perform the following tests to complete inspection: Upper comb plate testing & skirt indexing. Re-inspection required | 9/26/2025 |
| A17.1-2016 : Elevators | 7.17 - Step/skirt clearances, panels, and performance index | 6.1.3.3.5 | No | No | Need index print out to complete report. | 9/4/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Certificate | No | No | A current MO State operating certificate shall be posted near the equipment, in a noncombustible frame with a clear protective vision plate over it. | 9/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.14 - Code data plate | 8.9 | No | No | An individual data plate shall be provided indicating the code to be used for inspections and tests. The data plate shall be in plain view, securely attached to each main line disconnect or controller. The current data plate is not in plain view, and is marked for A17.1 1996. It should be marked for A17.1 2005. | 9/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.19 - Maintenance records | 8.6.1.4 | No | No | A start-up procedure shall be available to authorized personnel. | 9/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.3 - Handrails | 6.1.3.4 (Hand rails) (Re-Inspection) | Yes | No | The handrails shall be inspected for wear and cracks. | 9/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.3 - Handrails | 6.1.3.2 | Yes | No | The handrail speed monitor shall be tested. | 9/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3 Step/Skirt Performance Index | Yes | No | The skirt indexing test shall be performed. A test was performed which showed negative numbers for the loaded gap, which indicated the test was not performed properly. The test shall be repeated using the manufacturers instructions and requirements. | 9/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.7 - Combplate and comb step impact device | 6.1.3.6 | Yes | No | The upper comb impact horizontal center shall be tested. | 9/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.9 - Steps and upthrust device | 8.6.8.6 | Yes | No | The step upthrust device shall be tested. | 9/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.14 - Code data plate | 8.9 | No | No | Verify that a nameplate or data plate that specifies the required brake torque and meets the requirements of A17.1 2005 6.1.5.3 has been provided. | 9/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.4 - Drive machine and brake | 8.6.8.12 Brake | Yes | No | The brake torque shall be tested. | 9/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.10 - Missing step device | 6.1.6.5 | Yes | No | The missing step device shall be tested. | 9/12/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.11 - Step level device | 6.1.6.3.11 | Yes | No | The level step device shall be tested. | 9/12/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.5 - Lighting | 8.6.11.5(i) Demarcation Lighting (Re-Inspect) | Yes | No | The demarcation light operation shall be tested. | 9/12/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.14 - Code data plate | 8.9 | No | No | An individual data plate shall be provided indicating the code to be used for inspections and tests. The data plate shall be in plain view, securely attached to each main line disconnect or controller. The current data plate is not in plain view, and is marked for A17.1 1996. It should be marked for A17.1 2005. | 8/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.19 - Maintenance records | 8.6.1.4 | No | No | A start-up procedure shall be available to authorized personnel. | 8/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Certificate | No | No | A current MO State operating certificate shall be posted near the equipment, in a noncombustible frame with a clear protective vision plate over it. | 8/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.5 - Lighting | 8.6.11.5(i) Demarcation Lighting (Re-Inspect) | Yes | No | Replace all broken step demarcation sections. There are at least 3 witnessed. | 8/12/2026 |