Inspection
Inspection Details
Equipment ID
17922
17922
Inspection Date
7/5/2019
7/5/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Richard Dalman
Richard Dalman
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
15
15
External ID
6baf32db-16d4-4575-82c4-803f11541246
6baf32db-16d4-4575-82c4-803f11541246
Location
Argosy Casino Hotel
777 NW ARGOSY PKWY, RIVERSIDE, MO
Phone: (816) 746-3100
777 NW ARGOSY PKWY, RIVERSIDE, MO
Phone: (816) 746-3100
Owner
Argosy Casino
777 NW ARGOSY PKWY, RIVERSIDE, MO 64150-1512
777 NW ARGOSY PKWY, RIVERSIDE, MO 64150-1512
Billing
Attn: Argosy Casino
777 NW ARGOSY PKWY, RIVERSIDE, MO 64150-1512
777 NW ARGOSY PKWY, RIVERSIDE, MO 64150-1512
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | replace the phase 1 keyswitch collar, can no longer read the words on, off, bypass, or fire service on the collar | 11/23/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(c) | No | No | the monthly fire service test log is to be posted in the machine room | 11/23/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | a new copy of the state operating certificate is to be posted in the machine room every year | 11/23/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The state operating certificate posted in the machine room expired in 2011, update with a new copy when received from the state annually | 11/23/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | No | No | Monthly fire service test log has not been filled out monthly, test fire service monthly and fill out log in the machine room | 11/23/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Machine room maintenance logs have not been filled out since 2017, fill out log for every visit, callback, and maintenance | 11/23/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Fire service Phase 1 key switch color markings are no longer legible, replace collar with one that you can read (211.3a) | 11/23/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate posted in the machine room expired in 2011, update with current copy when received from the state of Missouri | 11/23/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | monthly fire service test log has not been filled out | 11/23/2025 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | replace burnt out machine room light bulbs | 11/23/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Replace older permits with updated permits in a displayable location | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | No | No | Owner responsible for updated monthly fire service log | |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit floor free of dust and debris | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Provide proper counterweight runby | |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | No | No | Replace damaged hoistway door relating cable - splitting wires | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The state operating certificate posted in the machine room expired in 2011, update with a new copy when received from the state annually; Repeat violation 8/26/2024 & 9/2/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Monthly fire service test log has not been filled out monthly, test fire service monthly and fill out log in the machine room; Repeat violation 8/26/2024 & 9/2/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.2 Callbacks (Trouble Calls) Documentation | No | No | Update PM log. Repeat 9/2/2025 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit | |
| A17.1-1996 : Elevators | 3.12 - Pipes, wiring, and ducts | 102 | No | No | Junction box cover missing on duct run between car one and two viable from car top at bottom landing |