Inspection
Inspection Details
Equipment ID
11048
11048
Inspection Date
7/28/2019
7/28/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Michael Collumbien
Michael Collumbien
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
f1d0c3fd-cd24-4548-a117-08e0c65a9fac
f1d0c3fd-cd24-4548-a117-08e0c65a9fac
Location
Pierre Laclede Center
7701 FORSYTH BLVD, CLAYTON, MO
Phone: (314) 862-2432
7701 FORSYTH BLVD, CLAYTON, MO
Phone: (314) 862-2432
Owner
CBRE
7733 FORSYTH BLVD STE 295, CLAYTON, MO 63105-1817
7733 FORSYTH BLVD STE 295, CLAYTON, MO 63105-1817
Billing
Attn: CBRE
7733 FORSYTH BLVD STE 295, SAINT LOUIS, MO 63105-1817
7733 FORSYTH BLVD STE 295, SAINT LOUIS, MO 63105-1817
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | The emergency power shall be tested with 125% of capacity. | 7/28/2019 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | Emergency/standby power operation of the elevators shall be operational. | 11/9/2021 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/26/2022 | ||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service checklist are missing. | 4/26/2022 | ||
A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | x | Car door restrictor shall work at all floors. | 6/26/2023 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | Pit shall be kept clean. Remove excess debris & oil. | 3/19/2024 | ||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 6/26/2023 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 7/18/2023 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Testing incomplete. Need to test: FS, EP, EQ, SOS, Buffers (car/cw), 100% safeties, 125% (hold & 1 floor run), slide. | 3/25/2024 | |
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Emergency lighting shall work. | 3/25/2024 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Alarm bell shall work with loss of main 120v power. | 3/25/2024 | |
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | MCP Fire service testing must be properly documented monthly on log sheet. | |||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Pit light shall work. | |||
A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | x | Ropes are rouged and need to be replaced. |