Inspection
Inspection Details
Equipment ID
14759
14759
Inspection Date
8/7/2019
8/7/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
871caad3-bf57-4c55-901d-c291f080f746
871caad3-bf57-4c55-901d-c291f080f746
Location
Hilton Hotel Airport
10330 NATURAL BRIDGE RD, SAINT LOUIS, MO
Phone: (314) 824-1600
10330 NATURAL BRIDGE RD, SAINT LOUIS, MO
Phone: (314) 824-1600
Owner
Hilton Hotel Airport
10330 NATURAL BRIDGE RD, SAINT LOUIS, MO 63134-3303
10330 NATURAL BRIDGE RD, SAINT LOUIS, MO 63134-3303
Billing
Attn: Hilton Hotel Airport
10330 NATURAL BRIDGE RD, SAINT LOUIS, MO 63134-3303
10330 NATURAL BRIDGE RD, SAINT LOUIS, MO 63134-3303
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Car dropped 2 1/2 during 15 minutes standing test control valve is leaking back into tank | 11/17/2020 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)2 | No | No | Car dropped 2 1/2" during 15 min. static test. Oil leaking back through control valve. Repair/replace valve. 2.32 | 11/17/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit of water and oil. | 11/17/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | A 17.1 5.1.1.1(e) PIT ACCESS, LIGHTING, STOP SWITCH, AND CONDITION - STANDING WATER IN PIT | 11/17/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit has been under water, need to clean pit | 11/16/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Machine room has been under water, need to clean machine including removing water from pump unit pan | 11/16/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in car are not guarded to prevent injury to passengers in event of bulb breakage. Install tubes and end caps over all bulbs or install solid panels in drop ceiling, not open egg crate type as in present. | 11/16/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired, replace or have serviced. | 11/16/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit has standing water, sump pump has been removed, need to replace sump pump | 11/16/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room | 11/16/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in car are not guarded to prevent injury to passengers in event of bulb breakage. Need to install tubes & end caps over all bulbs or install solid panels in drop ceiling, not open egg crate type | 11/16/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit has standing water, sump pump has been removed, need to replace sump pump | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the elevator machine room | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in the car are not guarded to prevent injury to passengers in event of bulb breakage. Install tubes and end caps over all bulbs or install solid panels in drop ceiling not open egg crate type as in at present. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit has standing water, sump pump has been removed, need to replace sump pump | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in the car are not guarded to prevent injury to passengers in event of bulb breakage. Install tubes and end caps over all bulbs or install solid panels in drop ceiling not open egg crate type as in at present. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Machine room shall be kept clean of grease and oil. |