Inspection
Inspection Details
Equipment ID
6919
6919
Inspection Date
8/9/2019
8/9/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
15
15
Governor Rope Pull
75/650
75/650
Door Closing Force
14
14
External ID
9fbbc443-f6a4-45dd-9ab6-25cfe1f40ff9
9fbbc443-f6a4-45dd-9ab6-25cfe1f40ff9
Location
St. Louis Marriott West
660 MARYVILLE CENTRE DR, SAINT LOUIS, MO
Phone: (314) 878-3005
660 MARYVILLE CENTRE DR, SAINT LOUIS, MO
Phone: (314) 878-3005
Owner
Attn: St. Louis Marriott West
PMO III, LLC
660 MARYVILLE CENTRE DR, SAINT LOUIS, MO 63141
Phone: (000) 000-0000
Email: accountspayable@stlmarriottwest.com
PMO III, LLC
660 MARYVILLE CENTRE DR, SAINT LOUIS, MO 63141
Phone: (000) 000-0000
Email: accountspayable@stlmarriottwest.com
Billing
Attn: St. Louis Marriott West
St. Louis Marriott West
660 MARYVILLE CENTRE DR, SAINT LOUIS, MO 63141
Phone: (000) 000-0000
Email: accountspayable@stlmarriottwest.com
St. Louis Marriott West
660 MARYVILLE CENTRE DR, SAINT LOUIS, MO 63141
Phone: (000) 000-0000
Email: accountspayable@stlmarriottwest.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | No monthly fire log. | 1/28/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating certificate. | 1/28/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Repair door knob in machine room. | 10/19/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated operating certificate in machine room. | 10/19/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Drain standing water from pit. | 1/4/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 2/26/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist ropes are showing signs of wear and stretching, need to replace the ropes within 60 days. Re-inspection required | 2/26/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 3/11/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 3/11/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 2/12/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The following tests need to be performed to complete 5 year inspection: full load, full speed car safeties, full load, full speed car buffer, counterweight safeties, 125% brake, overspeed governor jaw and switch speeds, overspeed governor pull thru, safeties pull out. Re-inspection required | 2/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Elevator lost traction before actuating top final limit switch. Red-tagged, Re-inspection required | 2/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Safety actuating arm appears to strike pit equipment when running down onto bottom final limit switch, repair same. Re-inspection required | 2/12/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The following tests need to be performed to complete 5 year inspection: full load, full speed car safeties, full load, full speed car buffer, counterweight safeties, 125% brake, overspeed governor jaw and switch speeds, overspeed governor pull thru, safeties pull out. Re-inspection required | 3/27/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 2/12/2026 |