Inspection
Inspection Details
Equipment ID
19679
19679
Inspection Date
6/16/2017
6/16/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
19
19
External ID
19679
19679
Location
Old Laclede Gas & Light Building
1017 Olive St, St. Louis, MO
Phone: (314) 436-9019
1017 Olive St, St. Louis, MO
Phone: (314) 436-9019
Owner
Double Delta Arizona LLC
1017 Olive St, Ste 1000 C, St. Louis, MO 63101
1017 Olive St, Ste 1000 C, St. Louis, MO 63101
Billing
Attn: Double Delta Arizona LLC
1017 Olive St, Ste 1000 C, , MO 63101
1017 Olive St, Ste 1000 C, , MO 63101
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post current state certificate in machine room | 4/25/2019 |
| conversion | conversion | n/a | No | No | Remove cover on lobby smoke detectors at the 3rd, 5th, 7th, & 8th floors | 4/25/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need a maintenance control program on site posted on controller | 7/15/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service testing and document on log in machine room | 7/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Repair phone in car | 7/15/2021 |
| MO Minimum : Elevators | (J) - Counterweights | (J)1 | No | No | Top right counterweight needs replacing | 5/23/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete need to crush car buffer and perform slide test | 5/28/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test and document on log in machine room | 6/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Investigate and repair severe motor coupling noise. | 4/13/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.1.1 | No | No | Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell is not working on battery back up. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency light is not working on battery back up. |