Inspection
Inspection Details
Equipment ID
20333
20333
Inspection Date
8/1/2019
8/1/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Richard DuFrenne
Richard DuFrenne
Relief Valve Pressure
520
520
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
a1c0c3bb-471a-42b4-90f8-d48fc22e8a2a
a1c0c3bb-471a-42b4-90f8-d48fc22e8a2a
Location
Grace Hill Settlement
2125 BISSELL ST, SAINT LOUIS, MO
2125 BISSELL ST, SAINT LOUIS, MO
Owner
Grace Hill Settlement House
2600 HADLEY ST, SAINT LOUIS, MO 63106-4021
2600 HADLEY ST, SAINT LOUIS, MO 63106-4021
Billing
Attn: Grace Hill Settlement House
2600 HADLEY ST, SAINT LOUIS, MO 63106-4021
2600 HADLEY ST, SAINT LOUIS, MO 63106-4021
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In cab emergency telephone shall work. | 1/25/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A monthly fire service testing log shall be kept on-site. | 11/13/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide MCP. | 11/13/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 3.18 | No | No | Jack head packing is worn and excessively leaking, repair immediately. | 11/13/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency alarm bell shall be operational when the 110v source is removed. | 8/16/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 2/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. | 2/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up-to-date operating certificate shall be posted in the machine room. | 3/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self-closing and self-locking. Door closer is not working. | 3/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 10/28/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | All non-elevator related materials shall be removed from machine room. | 8/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | A two-way communication means between the car and a location staffed by authorized personnel shall be provided. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | The pit lighting shall procvide an illumination of not less thean 100 xl (10fc) at the pit floor. |