Inspection
Inspection Details
Equipment ID
24278
24278
Inspection Date
8/7/2019
8/7/2019
Inspection Type
New Installation
New Installation
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Jacob Williams
Jacob Williams
Relief Valve Pressure
Slide
2"
2"
Governor Rope Pull
NA/200
NA/200
Door Closing Force
23
23
External ID
769c7590-0720-4020-a0a6-b18d175f7a03
769c7590-0720-4020-a0a6-b18d175f7a03
Location
St. Louis Community College Center for Nursing and Health Services
5500 Oakland Ave, St. Louis, MO
Phone: (314) 513-4200
Email: aknelch@tarltoncorp.com
5500 Oakland Ave, St. Louis, MO
Phone: (314) 513-4200
Email: aknelch@tarltoncorp.com
Owner
Attn: St. Louis Community College
St. Louis Community College
300 S Broadway, St. Louis, MO 63102
Phone: (314) 513-4200
Email: aknelch@tarltoncorp.com
St. Louis Community College
300 S Broadway, St. Louis, MO 63102
Phone: (314) 513-4200
Email: aknelch@tarltoncorp.com
Billing
Attn: Kone, Inc
Kone, Inc
9324 Dielman Industrail Drive, Olivette, MO 63132
Phone: (314) 991-1158
Email: rachel.mazzola@kone.com
Kone, Inc
9324 Dielman Industrail Drive, Olivette, MO 63132
Phone: (314) 991-1158
Email: rachel.mazzola@kone.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.2-2014 : Elevators | 1.6 - Car emergency signal | 1.6.1 | Yes | No | The emergency phone shall work with 24/7 support. | 11/11/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator machine room. | 9/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 12/8/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 8/18/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 12/6/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. (2nd Notice) | 12/6/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | 2.11.11.8 - Fire guides are missing from the hoistway door. | 12/6/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 10/18/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Fire gibs are missing from some of the hoistway doors. | 10/18/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | Inspection and testing incomplete. Remaining items: 125% 1 floor run down, 0% up unintended motion and 125% down unintended motion, 100% safety set, slide, EBR, governor pullout and pull-thru, elect/mech speeds. | 8/23/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | MCP Fire Service testing must be properly documented monthly on log sheet. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Non-elevator related items shall not be stored in machine room. | |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.7.2 Seizing of Rope Ends | No | No | 2.20.9.7.2 - Suspension rope tail ends shall be properly seized/banded. | |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.5 Wedge Rope Sockets | No | No | Hoist rope tail end retaining clips shall be properly spaced. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.28 - Counterweight and counterweight buffer | 2.21 | No | No | 2.21.1.2 - Counterweight hold down clamps need to be set properly. They are currently 3" above weight stack. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. Remove excess debris. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |