Inspection
Inspection Details
Equipment ID
19095
19095
Inspection Date
8/5/2019
8/5/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Kurt Warttig
Kurt Warttig
Relief Valve Pressure
640
640
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
5b8445da-b401-49cd-9121-bff81fe36459
5b8445da-b401-49cd-9121-bff81fe36459
Location
Holt High School
600 CAMPUS DR, WENTZVILLE, MO
Phone: (636) 327-3858
600 CAMPUS DR, WENTZVILLE, MO
Phone: (636) 327-3858
Owner
Attn: Linda Bagby
Wentzville R-IV School District
1 CAMPUS DR, WENTZVILLE, MO 63385
Phone: (636) 327-3858 Ext: 21323
Email: lindabagby@wsdr4.org
Wentzville R-IV School District
1 CAMPUS DR, WENTZVILLE, MO 63385
Phone: (636) 327-3858 Ext: 21323
Email: lindabagby@wsdr4.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | fire Extinguisher not in machine room | 1/3/2019 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Firefighters emergency service phase 2 signage in car is illegible. Replace signage | 4/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written maintenance control program shall be kept on site for each elevator | 4/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | Yes | No | Observed that sump pump was not plugged in. Determine if sump pump works correctly, plug in. | 7/24/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide current year documents for the MCP on site | 7/24/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current certificate. | 7/24/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current certificate in machine room | 3/4/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone line not working | 11/6/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lights are not working. Re-inspection required | 6/24/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 3/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired, have serviced or replaced |