Inspection
Inspection Details
Equipment ID
5193
5193
Inspection Date
8/14/2019
8/14/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
24
24
External ID
14b681d6-e57b-4518-8719-d2cf8484a70e
14b681d6-e57b-4518-8719-d2cf8484a70e
Location
Castle Park Apartments
1600 CASTLE PARK DR, SAINT LOUIS, MO
Phone: (314) 725-0666
1600 CASTLE PARK DR, SAINT LOUIS, MO
Phone: (314) 725-0666
Owner
Castle Park Apartments
1600 CASTLE PARK DR, SAINT LOUIS, MO 63133-1801
1600 CASTLE PARK DR, SAINT LOUIS, MO 63133-1801
Billing
Attn: Castle Park Apartments
Gregory or Carter Lyons
1600 CASTLE PARK DR, SAINT LOUIS, MO 63133-1801
Gregory or Carter Lyons
1600 CASTLE PARK DR, SAINT LOUIS, MO 63133-1801
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 10/22/2018 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate in the elevator machine room. | 11/11/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall have a code compliant lock. | 11/11/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Clean the pit. | 11/11/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 12/7/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | On Phase 2 fire service, the doors shall open with continuous pressure only on the door open button. | 9/18/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | On Phase 2 fire service, the doors shall close with continuous pressure only on the door close button. | 9/18/2023 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a code compliant MCP including on-site documents. No monthly fire service checklist. | 4/6/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | The pit shall be kept clean. | 4/6/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | Yes | On Phase 2 fire service, the doors shall open with continuous pressure only on the door open button. Originally cited 8/24/2022 and still not corrected. Elevator Red Tagged. | 4/26/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | Yes | On Phase 2 fire service, the doors shall close with continuous pressure only on the door close button. Originally cited 8/24/2022 and still not corrected. Elevator Red Tagged. | 4/26/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | Yes | No | The pit shall be kept clean. Remove excess debris. This violation has been self-certified by the location multiple times and has not been taken care of. Re-inspection now required for this violaiton. | 4/26/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Note: No monthly fire service log present. MCP has not been updated since 2021. | 5/7/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work with and without main power and give proper location. | 4/26/2024 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency lighting shall be operational. | 4/26/2024 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor shall work at all floors. | 4/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing car station screws. 9 of 10 screws are missing. | 5/7/2024 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Machine room door shall be self-closing and self-locking. | 5/7/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Controller door off hinges, repair and re-install properly. | 5/7/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Replace broken hoistway door closer hardware (including but not limited to floor 1). | 5/7/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | Yes | 2-way communication device shall work with and without main power and give proper location. Red Tag remains until fixed. | 5/7/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/20/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | Yes | No | The fire service key switch on the 1st floor needs a new bezel. | 8/20/2026 |
| MO Minimum : Elevators | (J) - Counterweights | (J)3 | Yes | No | Counterweights hit spring buffer before car reached top final limit. Suspension ropes must be shortened. |