Inspection
Inspection Details
Equipment ID
23268
23268
Inspection Date
8/14/2019
8/14/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
670
670
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
cd12e28e-80fd-4b86-9be3-44be5fd10f19
cd12e28e-80fd-4b86-9be3-44be5fd10f19
Location
The Boulevard
3330 EHLMANN RD, SAINT CHARLES, MO
3330 EHLMANN RD, SAINT CHARLES, MO
Owner
Attn: O'Reilly Development Company LLC
O'Reilly Development Company LLC
431 S JEFFERSON AVE STE 116-C, SPRINGFIELD, MO 65806
Phone: (417) 893-6006
Email: tika@oreillydevelopment.com
O'Reilly Development Company LLC
431 S JEFFERSON AVE STE 116-C, SPRINGFIELD, MO 65806
Phone: (417) 893-6006
Email: tika@oreillydevelopment.com
Billing
Attn: O'Reilly Development Company LLC
O'Reilly Development Company LLC
5051 S NATIONAL AVE STE 4-100, SPRINGFIELD, MO 65810
Phone: (417) 893-6006
Email: tika@oreillydevelopment.com
O'Reilly Development Company LLC
5051 S NATIONAL AVE STE 4-100, SPRINGFIELD, MO 65810
Phone: (417) 893-6006
Email: tika@oreillydevelopment.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a code compliant MCP including onsite documents. | 10/26/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/26/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 9/27/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. Based on the installation year, the unit is overdue for a category 5 test. The overspeed valve shall be tested with the rated load on or before the next annual inspection. | 10/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car telephone shall be operational. | 2/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The emergency power indicator light in the main elevator lobby shall illuminate when the car is running on the emergency standby power. | 2/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of the findings for firefighters service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation and the date shall be available on site. | 2/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | No | No | Each elevator in the building shall be assigned a unique aphabetical or numerical identification adjacent to or on every elevator entrance at the designated level. | 2/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | Yes | No | The overspeed valve is not properly sealed. It shall be tested with the rated load within 90 days. | 2/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 2/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car telephone shall be operational. On auxiliary power, it does not respond when the button is pressed. On normal power the phone dials out, but is never connected to an operator. | 10/10/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The relief valve test shall be performed. | 10/10/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The low pressure switch shall be tested. | 10/10/2025 |