Inspection
Inspection Details
Equipment ID
1122
1122
Inspection Date
8/16/2019
8/16/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Joseph Jensen
Joseph Jensen
Mechanic Name
Relief Valve Pressure
470
470
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
abe25f93-a44b-4030-a971-d435a0c8654d
abe25f93-a44b-4030-a971-d435a0c8654d
Location
JCK Library
415 E CLARK ST, WARRENSBURG, MO
Phone: (660) 543-4964
415 E CLARK ST, WARRENSBURG, MO
Phone: (660) 543-4964
Owner
Attn: University of Central Missouri
University of Central Missouri
116 S, CLARK ST, WARRENSBURG, MO 64093
Phone: (000) 000-0000
Email: fpo_bus_ops@ucmo.edu
University of Central Missouri
116 S, CLARK ST, WARRENSBURG, MO 64093
Phone: (000) 000-0000
Email: fpo_bus_ops@ucmo.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency phone not working no dial tone | 9/17/2018 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)1 | No | No | elevator settling 2 1/2" in 15 min-shut machine room valve--no settling-oil leaking back thru control balve. Repair or replace | 9/17/2018 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certifiate in machine room | 8/28/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Oil tank lid ahould be modified to provide safe access by maintenance personnel to valve and pump and prevent damage to oil coolers. 120v outlet to power oil coolers on # 2 nonfunctional | 8/27/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 8/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | In case of fire don't use elevator signage needed | 9/3/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | In case of fire don't use elevator signage needed | 11/22/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | missing "in case of fire" sign at lobby | 11/22/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | door closing pressure above 30 lbs | 7/6/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Emergency battery lowering not working. Batteries | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MCP needed | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Light bulb burnt out |