Inspection
Inspection Details
Equipment ID
16910
16910
Inspection Date
8/21/2019
8/21/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Thomas Droege
Thomas Droege
Relief Valve Pressure
580
580
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
37d30127-f64e-470b-9847-61ae7ecd1563
37d30127-f64e-470b-9847-61ae7ecd1563
Location
The Garden @ Renaissance
3117 THOMAS ST, SAINT LOUIS, MO
Phone: (314) 652-8900
3117 THOMAS ST, SAINT LOUIS, MO
Phone: (314) 652-8900
Owner
Attn: McCormack, Baron Ragan
McCormack, Baron Ragan
3217 MARTIN LUTHER KING DR, ST. LOUIS, MO 63101
Phone: (314) 652-8900
McCormack, Baron Ragan
3217 MARTIN LUTHER KING DR, ST. LOUIS, MO 63101
Phone: (314) 652-8900
Billing
Attn: Senior Livings & Gardens @ Renaissance
Senior Livings & Gardens @ Renaissance
3217 MARTIN LUTHER KING DR, ST. LOUIS, MO 63106
Phone: (314) 652-8900
Email: ebonie.turner@mccormackbaron.com
Senior Livings & Gardens @ Renaissance
3217 MARTIN LUTHER KING DR, ST. LOUIS, MO 63106
Phone: (314) 652-8900
Email: ebonie.turner@mccormackbaron.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace damaged fire service signage in car. | 4/18/2019 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 1001.2(b)(11) | No | No | Where additional power source is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. (Confirm operation and correct if needed) | 3/24/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | The auxiliary battery lowering shall be operational. | 11/16/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 3/24/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. | 9/27/2023 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | Yes | No | Where additional power source is connected to load side of the disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is open. | 9/27/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate in machine room. | 3/24/2025 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Provide a current tested Fire Extinguisher in machine room. | 3/31/2025 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Machine room lighting shall properly operate. | 3/24/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit lighting shall be operational. | 3/31/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up-to-date operating certificate is required in the machine room. | 3/24/2025 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Machine room lights shall work. | 3/17/2025 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | Yes | No | Auxiliary battery lowering worked, but appeared that auxiliary contacts have not been installed. Where additional power source is connected to load side of the disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is open. | 6/12/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit light shall work. | 3/24/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering does not work. Battery lowering shall be operational and the disconnect shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is open. | 2/13/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the machine room. | 3/24/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 207.8 | Yes | No | Battery lowering does not work or have batteries. Battery lowering shall be operational and the disconnect shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is open. Note: This is the final notice for this violation. Failure to correct the violation will result in the elevator being red tagged and locked out of service. |