Inspection
Inspection Details
Equipment ID
7865
7865
Inspection Date
8/30/2019
8/30/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
24
24
Governor Rope Pull
100/425
100/425
Door Closing Force
18
18
External ID
12e0db66-0fb9-409d-a698-a668f7b0ed5b
12e0db66-0fb9-409d-a698-a668f7b0ed5b
Location
DEA of St. Louis
317 S 16TH ST, SAINT LOUIS, MO
Phone: (314) 538-4600
317 S 16TH ST, SAINT LOUIS, MO
Phone: (314) 538-4600
Owner
NGPV St Louis MO LLC
1650 TYSONS BLVD STE 1500, MCLEAN, VA 22102-4845
1650 TYSONS BLVD STE 1500, MCLEAN, VA 22102-4845
Billing
Attn: NGPV St Louis MO LLCColliers Internationa c/o l
1650 TYSONS BLVD STE 1500, MCLEAN, VA 22102-4845
1650 TYSONS BLVD STE 1500, MCLEAN, VA 22102-4845
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.18 - Traction drive machines | 208 | No | No | Machine will not pick up rated capacity due to load weight being out of calibration. | 9/30/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light does not work. | 10/7/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell does not work. | 10/7/2020 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1202.14 | Yes | No | Four (4) suspension ropes are out of their sleeves on the counterweight side. | 10/7/2020 |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 202 | Yes | No | Missing two lock nuts on the bottom of the counterweights. | 10/7/2020 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 1001.2(b)(8) | No | No | Greenfield feeding the bottom slow down limit is broken. Repair so that there are no exposed wires. | 10/31/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide MCP | 9/30/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm inoperable on battery, also emergency light. Re-inspection required | 10/6/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Unable to communicate with emergency personnel over phone. Re-inspection required | 12/15/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Place current state operating certificate in elevator machine room | 7/21/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform the following tests to complete the inspection: full speed counterweight buffer, full load, full speed, car buffer, 125% brake, full load, full speed car safeties, pull out, pull thru, overspeed governor switch and jaw speeds. Re-inspection requireds | 10/30/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator stopped operating during testing, need to perform testing of emergency fire service to complete inspection. Re-inspection required | 8/27/2025 |