Inspection
Inspection Details
Equipment ID
10464
10464
Inspection Date
3/28/2018
3/28/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Parker
Dennis Parker
Mechanic Name
Relief Valve Pressure
Slide
10
10
Governor Rope Pull
320/500
320/500
Door Closing Force
23
23
External ID
Location
Gallery 400
400 Washington Ave, St. Louis, MO
Phone: (314) 540-5988
400 Washington Ave, St. Louis, MO
Phone: (314) 540-5988
Owner
BrandonView LLC
4140 Washington, St. Louis, MO 63108
4140 Washington, St. Louis, MO 63108
Billing
Attn: BrandonView LLC
400 Washington Ave, , MO 63102
400 Washington Ave, , MO 63102
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | Install Box covers on all uncovered electrical boxes | 8/21/2018 | ||
| conversion | conversion | n/a | Remove unused and Excessive draped flex conduit.Shorten as needed fasten to wall and cieling | 8/21/2018 | ||
| conversion | conversion | n/a | Shorten hoist ropes c measurment | 8/21/2018 | ||
| conversion | conversion | n/a | Furnish permanent outlet for air conditioner (no extension cords) | 8/21/2018 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Provide permanent means of water removal from the elevator pit. | 8/9/2019 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 5/4/2021 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. | 5/4/2021 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | The elevator buffer has been submerged recently resulting in water contaminating the oil reservoir for the buffer. The car buffer shall be cleaned/contaminated water removed and the proper weight buffer oil used in the reservoir. | 8/7/2023 | ||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 8/7/2023 | ||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Pit light does not work | 8/3/2023 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current operating certificate shall be displayed in the machine room | 3/21/2024 | ||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Light in pit shall work | 3/21/2024 |