Inspection
Inspection Details
Equipment ID
21310
21310
Inspection Date
9/11/2019
9/11/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Jerry Reasoner
Jerry Reasoner
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
7eeca2cf-6f57-4f93-8603-8daf31b1e729
7eeca2cf-6f57-4f93-8603-8daf31b1e729
Location
William Jewell College-Pryor Center
500 COLLEGE HL, LIBERTY, MO
Phone: (816) 781-7700
500 COLLEGE HL, LIBERTY, MO
Phone: (816) 781-7700
Owner
William Jewel College
500 COLLEGE HL, LIBERTY, MO 64068-1843
500 COLLEGE HL, LIBERTY, MO 64068-1843
Billing
Attn: William Jewel College
500 COLLEGE HL # 1110, LIBERTY, MO 64068-1843
500 COLLEGE HL # 1110, LIBERTY, MO 64068-1843
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | Need to post code data plate on controller. "A17.1-2004" | 4/13/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | Test and log firefighter operation monthly | 4/13/2021 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | Post emergency evacuation of passengers form inside machine room | 4/13/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate inside control space | 4/13/2021 | ||
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 Runby (Re-Inspect) | x | Shorten hoist ropes for proper runby. | 9/20/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state operating certificate inside the machine room | 11/7/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.11.1 | Test and log firefighter operation monthly | 11/7/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | State operating certificate not displayed in control space | 11/7/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not operate | 10/1/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | State operating certificate not displayed | 11/7/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | need mach space lt sw next to door jamb top floor | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.8 | need mach.space stop sw in mach space 2.7.3.5 |