Inspection
Inspection Details
Equipment ID
18669
18669
Inspection Date
3/28/2018
3/28/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Parker
Dennis Parker
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
Location
AmeriStar Casino
#1 AmeriStar Blvd, St. Charles, MO
Phone: (636) 940-4300
#1 AmeriStar Blvd, St. Charles, MO
Phone: (636) 940-4300
Owner
AmeriStar Casino- St. Charles LLC
1260 S Main St, St. Charles, MO 63301
1260 S Main St, St. Charles, MO 63301
Billing
Attn: AmeriStar Casino- St. Charles, LLC
# 1 AmeriStar Blvd, , MO 63301
# 1 AmeriStar Blvd, , MO 63301
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Replace hoist cables (Rouge) | 10/1/2018 | ||
conversion | conversion | conversion - reinspect | x | Seismic not working | 3/27/2019 | |
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | Replace ceiling panels or guard bulbs inside cab. | 5/26/2020 | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display updated certificate in machine room. | 5/26/2020 | ||
A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5c Receptacles | Replace bulbs that are out in machine room. | 5/26/2020 | ||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Update fire extinguisher in machine room. | 5/26/2020 | ||
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | All lights in the elevator cab shall be protected or be above the drop ceiling. | 5/26/2020 | ||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | The cab ceiling is of the open type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | 7/27/2023 | ||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | A number of lighting fixtures in the elevator cab have been damaged and shall be repaired to at least provide not less than five (5) foot-candles of lighting throughout the cab. | 7/27/2023 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | The emergency light fixture inside the elevator is not operational and shall be repaired. Reinspection required. | 4/10/2023 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | The cab ceiling is of the open type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | 7/27/2023 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | A hoistway door fire tab is missing on the 3rd floor. Reinstall fire tab at the location noted. | 7/27/2023 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys (Re-Inspection) | x | The fireman’s service phase I key switch has degraded and shall be replaced. The key switch will not allow the phase I key to be removed without great difficulty. | 4/10/2023 | |
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.7 Firefighters’ Emergency Operation: Operating Procedures (Signage) | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The “call cancel” button is not labeled inside the car and shall be labeled correctly. | 7/27/2023 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | x | The key switch will not allow the phase I key to be removed without great difficulty. | 2/13/2024 |