Inspection
Inspection Details
Equipment ID
11834
11834
Inspection Date
8/29/2019
8/29/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
63aa8c66-4bd4-495e-a0a8-216912a021c9
63aa8c66-4bd4-495e-a0a8-216912a021c9
Location
Graybar Electric- Clayton
34 N MERAMEC AVE, CLAYTON, MO
Phone: (314) 713-3393
34 N MERAMEC AVE, CLAYTON, MO
Phone: (314) 713-3393
Owner
Graybar Electric- Clayton
34 N MERAMEC AVE, CLAYTON, MO 63105-3941
34 N MERAMEC AVE, CLAYTON, MO 63105-3941
Billing
Attn: Graybar Electric
34 N MERAMEC AVE, CLAYTON, MO 63105-3941
34 N MERAMEC AVE, CLAYTON, MO 63105-3941
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 8/29/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/27/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 9/27/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | A category 5 test shall be performed. | 3/4/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | Fire service in car audible signal shall be operational. | 3/4/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency/standby power operation of the elevator shall be tested. | 3/4/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Yes | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Currently schematics, controller manual, maintenance log, and call-back log are present. | 5/24/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | Emergency power test failed. The elevator shall be able to operate while being powered by the emergency generator. | 5/24/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | The building work in progress includes a remote fire control panel. When work is complete, the tests and requirements of A17.2 item 6.4, A17.1-2005 - 8.10.2.2.6 shall apply. | 5/24/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 11/15/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency power must be tested annually. | 7/24/2024 |