Inspection
Inspection Details
Equipment ID
6612
6612
Inspection Date
3/16/2018
3/16/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Relief Valve Pressure
460
460
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
22/15
22/15
External ID
6612
6612
Location
Boeing- Bldg 598
2600 North 3rd St, St. Charles, MO
Phone: (314) 705-0516
2600 North 3rd St, St. Charles, MO
Phone: (314) 705-0516
Owner
Boeing Co
MC-S221-1400 PO Box 516, St Louis, MO 63166-0516
MC-S221-1400 PO Box 516, St Louis, MO 63166-0516
Billing
Attn: Boeing Co
PO Box 516 MC S221-1400, , MO 63166-0516
PO Box 516 MC S221-1400, , MO 63166-0516
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | Need a maintenance control program on site | 10/22/2025 | ||
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | x | Overspeed valve testing is past due. Tessting to be completed in 30 days are less otherwise unit will be red tagged out of service | 7/10/2025 | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Fire service call cancel button shall work. 14 days to be corrected and re-inspected or unit to be red tagged. | 10/22/2025 | |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | x | Fire service phase 2 key switch shall have only 2 positions. Unit does not have "HOLD". Bezel is correct with only "OFF" and "ON". | 10/22/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 10/22/2025 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | This repair/alteration inspection included witnessing working pressure and relief pressure. The working pressure was 340#. While testing for relief pressure, the unit went down. This inspection was not completed. Relief valve pressure shall be successfully tested. | 2/26/2026 | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Fire service call cancel button shall work. 14 days to be corrected and re-inspected or unit to be red tagged. Violation unable to be checked at time of alteration inspection on 10/16/25 due to unit going down. | 2/26/2026 | |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | x | Fire service phase 2 key switch shall have only 2 positions. Unit does not have "HOLD". Bezel is correct with only "OFF" and "ON". Violation unable to be checked at time of alteration inspection on 10/16/25 due to unit going down. | 2/26/2026 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | x | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 2/26/2026 | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Fire service call cancel button shall work. | ||
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | Fire service phase 2 key switch shall have only 2 positions. Unit does not have "HOLD". Bezel is correct with only "OFF" and "ON". |