Inspection
Inspection Details
Equipment ID
11872
11872
Inspection Date
8/22/2019
8/22/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
John Wiesehan
John Wiesehan
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
85852e6b-af45-4c7f-a98f-cdadbd4ee7a4
85852e6b-af45-4c7f-a98f-cdadbd4ee7a4
Location
The Dorchester
665 S SKINKER BLVD, SAINT LOUIS, MO
Phone: (314) 721-8181
665 S SKINKER BLVD, SAINT LOUIS, MO
Phone: (314) 721-8181
Owner
Attn: The Dorchester
The Dorchester
665 S SKINKER BLVD, SAINT LOUIS, MO 63105
Phone: (000) 000-0000
The Dorchester
665 S SKINKER BLVD, SAINT LOUIS, MO 63105
Phone: (000) 000-0000
Billing
Attn: The Dorchester
The Dorchester
665 S SKINKER BLVD, SAINT LOUIS, MO 63105
Phone: (000) 000-0000
Email: kbozoian@macapartments.com
The Dorchester
665 S SKINKER BLVD, SAINT LOUIS, MO 63105
Phone: (000) 000-0000
Email: kbozoian@macapartments.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | Phase 2 fire service shall work. | 8/22/2019 |
| A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 1002.3a | Yes | Yes | A category 5 full load test shall be scheduled in the 2019 calendar year. | 8/22/2019 |
| A17.1-1996 : Elevators | 2.13 - Governor,overspeed switch and seal | 1002.3b | Yes | Yes | A category 5 full load test shall be scheduled in the 2019 calendar year. | 8/22/2019 |
| A17.1-1996 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 1002.3f | Yes | No | A category 5 full load test shall be scheduled in the 2019 calendar year. | 8/22/2019 |
| A17.1-1996 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 1001.2(e)(2) | Yes | No | Provide code compliant minimum counterweight runby. | 2/6/2020 |
| A17.1-1996 : Elevators | 1.2 - Stop switches | 1001.2(a)(2) | No | No | The in car stop switch is broken. Repair or replace as needed. | 1/5/2022 |
| A17.1-1996 : Elevators | 2.27 - Rope fastenings | 1001.2(b)(25) | No | No | The wire-rope retaining clips shall be properly installed. At least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope (see Figure 2.20.9.5). The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. | 1/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The hoist rope and governor rope data tags are missing. | 1/5/2022 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 1001.2(b)(11) | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 1/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Install a code data plate. It shall read: Missouri Minimums & A17.1-1996. | 1/5/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit light is broken. Repair or replace as needed. | 1/5/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 1/26/2023 |
| A17.1-1996 : Elevators | 1.2 - Stop switches | 210.2(e) | Yes | No | Replace faulty in-car stop switch. | 2/23/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP, including PM records and monthly fire service test log, not being properly documented. | 2/28/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit light shall work. | 2/28/2024 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 100 | No | No | Hoistways shall be of solid construction. Repair hole in hoistway wall (at 3, 4" x 8" hole to pipe chase). | 2/28/2024 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | No | No | The car top shall be clean. | 2/28/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. 2022 MCP records are missing. | 2/28/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Remove temporary wiring (extension cord) and replace with permanent wiring to meet NEC | 7/9/2025 |