Inspection
Inspection Details
Equipment ID
19128
19128
Inspection Date
9/18/2019
9/18/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Bobby Joe Mehrens
Bobby Joe Mehrens
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
25
25
External ID
d699e47e-b9e9-438c-8fed-d683ec117eeb
d699e47e-b9e9-438c-8fed-d683ec117eeb
Location
Phi Gamma
851BOWLES DR, LIBERTY, MO
Phone: (816) 365-7641
851BOWLES DR, LIBERTY, MO
Phone: (816) 365-7641
Owner
William Jewel College
500 COLLEGE HL, LIBERTY, MO 64068-1843
500 COLLEGE HL, LIBERTY, MO 64068-1843
Billing
Attn: William Jewel College
500 COLLEGE HL # 1110, LIBERTY, MO 64068-1843
500 COLLEGE HL # 1110, LIBERTY, MO 64068-1843
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Emergency phone does not operate | 4/13/2021 | ||
conversion | conversion | n/a | Need to post fire service instructions inside elevator. | 4/13/2021 | ||
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Test and log firefighter operation monthly. | 4/13/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate inside machine room. | 4/13/2021 | ||
A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Remove debris from pit | 4/13/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.4 Car top light and Outlet | Top of car light does not illuminate. | 4/13/2021 | ||
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Post emergency evacuation of passengers form inside machine room. | 4/13/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.3 - Top-of-car operating device | 2.26.1.4 | Machine room inspection will not run elevator in up direction, only down direction. | 4/13/2021 | ||
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Test and log firefighter operation monthly | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state operating certificate inside the machine room | |||
A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No documentation of maintenance performed in maintenance record log | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | Post In Case of Fire signage next to hall button fixture at each landing | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | State operating certificate not displayed in control space | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | Post In Case of Fire signage next to hall button fixture at each landing | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not operate | 10/22/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | State operating certificate not displayed |