Inspection
Inspection Details
Equipment ID
1680
1680
Inspection Date
9/23/2019
9/23/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Tim Crafton
Tim Crafton
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
SOFT SET
SOFT SET
Governor Rope Pull
SOFT SET
SOFT SET
Door Closing Force
15
15
External ID
a35d7d85-e122-4b2f-8b3f-3b7d8d6baa9f
a35d7d85-e122-4b2f-8b3f-3b7d8d6baa9f
Location
Wainwright State Office Bldg
111 N 7TH ST RM 111, SAINT LOUIS, MO
Phone: (314) 340-6801
111 N 7TH ST RM 111, SAINT LOUIS, MO
Phone: (314) 340-6801
Owner
Attn: INTERAGENCY
Wainwright Building-INTERAGENCY
111 N 7TH ST RM 111, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Wainwright Building-INTERAGENCY
111 N 7TH ST RM 111, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Billing
Attn: INTERAGENCY
Wainwright Building-OAFMDC
111 N 7TH ST RM 111, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Wainwright Building-OAFMDC
111 N 7TH ST RM 111, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Need to finish inspection. Test gov., car buffer, pullout/pullthrough, car safeties, emergency brake, check hoistway, check car top, FEO, door closing force. | 9/23/2019 |
| conversion | conversion | n/a | No | No | Machine growling sound. Should be inspected by elevator company. | 9/23/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.18 - Traction drive machines | 2.24 | No | No | EXCESSIVE NOISE IN GEAR CASE, should be inspected by elevator company. | 12/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | Yes | No | Provide testing of Phase I operation. | 4/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | Yes | No | Provide testing of Phase II operation. | 4/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of elevator emergency power selector switch. | 4/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of elevator on emergency power. | 4/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc)(1) Wire ropes shall be replaced | Yes | Yes | Wire ropes found to be rouged, undersized and broken lays. Unit removed from service. Replace ropes. | 4/21/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide full load car buffer test. | 4/21/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide 125% brake test. | 4/21/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide full load car safety test, record slide. | 4/21/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state elevator certificate. | 4/21/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the elevator emergency power selector switch. |