MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
1. Lighting in the machine room shall be not less than ten (10) foot-candles at floor level. The lighting on the upper portion of the machine room, where the machine is located has no lighting.
|
12/6/2018
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
x
|
|
1) All electric elevators shall have a labeled emergency stop switch. The switch shall be located on or adjacent to the operating panel. There is no stop switch labeled in elevator. Only a door hold button. This shall be corrected. Ref: (F)1 Re-inspect
|
1/10/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
x
|
1) The driving-machine brake shall be maintained to ensure proper operations. When hall door interlock was tripped car continued to move about 2-3 feet. Ref: 8.6.4.6.1
|
7/29/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
2) Emergency communications shall be tested to determine conformance with the applicable requirements. Phone was tested several times and there was no response to call. Ref: 8.6.4.19.15
|
7/29/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
3) A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. Ref: 8.6.1.2.1
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
1) A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. Ref: 8.6.1.2.1
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Unit stopped working.
|
4/20/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Car door restrictor is not working. Re-inspection required
|
8/2/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
x
|
|
Door restrictor is out of adjustment, repair as needed.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
|