Inspection
Inspection Details
Equipment ID
11464
11464
Inspection Date
3/13/2018
3/13/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
560
560
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
Location
10th Street Offices
415 North 10th St, St. Louis, MO
Phone: (314) 231-0770
415 North 10th St, St. Louis, MO
Phone: (314) 231-0770
Owner
Keane Properties, LLC
135 W. Adams Ave, Kirkwood, MO 63122
135 W. Adams Ave, Kirkwood, MO 63122
Billing
Attn: Keane Properties, LLC
135 W. Adams Ave, , MO 63122
135 W. Adams Ave, , MO 63122
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | The car door restrictor device needs to be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. This will require a reinspection for compliance. | 3/5/2019 | |
| conversion | conversion | n/a | The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2005. | 10/1/2018 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not working properly. Check and repair this phone for proper operation and passenger safety. Reinspection required. | 9/11/2019 | |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | x | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 9/11/2019 | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2005. | 5/11/2020 | ||
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2005. | 5/11/2020 | ||
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)8 | x | x | Overspeed governor jaw set at too high of a rate of speed, must be below 175 fpm. Red-tag & Re-inspection required | 4/1/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Provide guards on bulbs to prevent accidental contact or breakage. | 4/5/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Cab floor tile is worn, has hole. Tripping hazard, replace. | 4/5/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher in machine room is expired, have serviced or replaced | 4/5/2025 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Provide guards on machine room bulbs, to prevent accidental contact or breakage | 4/5/2025 |