Inspection
Inspection Details
Equipment ID
21135
21135
Inspection Date
9/27/2019
9/27/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Wayne Ingram
Wayne Ingram
Mechanic Name
Jeremiah Dugger
Jeremiah Dugger
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
10eb2fce-5d49-4f48-958a-517929b03fe2
10eb2fce-5d49-4f48-958a-517929b03fe2
Location
Bear Village Student Housing
815 S KIMBROUGH AVE, SPRINGFIELD, MO
Phone: (417) 864-6303
815 S KIMBROUGH AVE, SPRINGFIELD, MO
Phone: (417) 864-6303
Owner
Attn: Bryan Properties
Bryan Properties
519 E. Walnut st, SPRINGFIELD, MO 65806
Phone: (417) 864-6303
Email: brad@bryan-properties.net
Bryan Properties
519 E. Walnut st, SPRINGFIELD, MO 65806
Phone: (417) 864-6303
Email: brad@bryan-properties.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.3 Provide Auxiliary Lighting | Yes | No | Replace the emergency light battery | 7/2/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. | 2/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | Have the fire extinguisher re-certified | 2/1/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 2/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Have the expired fire extinguisher re-certified | 6/6/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 6/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Remove all the stored paint from the machine room | 6/6/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide an MCP in the machine room | 6/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.3 Provide Auxiliary Lighting | Yes | No | Replace the bad emergency light battery | 6/3/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Replace the missing emergency light in the car. | 6/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 2.26.12 | No | No | Replace the missing Pictographic signage on the 1st. and 4th. floors | 6/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 2.26.12 | No | No | Replace the missing *1 Braille plate on the first floor | 6/6/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair the broken hall call station on the 4th.floor | 6/6/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Remove the stored cart from the elevator machine room. | 6/6/2024 |