Inspection
Inspection Details
Equipment ID
16883
16883
Inspection Date
9/20/2019
9/20/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
74c24c39-040d-429a-a12d-bd97a143f870
74c24c39-040d-429a-a12d-bd97a143f870
Location
Bed Bath & Beyond
8340 EAGER RD, SAINT LOUIS, MO
Phone: (314) 727-9300 Ext: 101
8340 EAGER RD, SAINT LOUIS, MO
Phone: (314) 727-9300 Ext: 101
Owner
Attn: UNK
Meridian Buildings DCM Group
8340 Eager Rd, SAINT LOUIS, MO 63144
Phone: (000) 000-0000
Meridian Buildings DCM Group
8340 Eager Rd, SAINT LOUIS, MO 63144
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. | 2/5/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | On initial phase I, fire recall at the alternate level, the door open button does not work. Repair | 2/5/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Red Tag) | Yes | Yes | Phone in elevator cab does not work. | 11/19/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control program. | 4/26/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV installed and not sealed. Perform OSV test on or before next annual inspection. | 4/26/2022 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 110 | No | No | Hoistway door closer missing, repair as needed. BOTH FLOORS. | 4/19/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Update MCP. Has ‘21 docs, needs ‘22. | 4/19/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Phase II not working, repair as needed. 15 days to repair and reinspect. 3/1/22 | 4/28/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate has expired | 5/10/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is inoperative. Re-inspection required | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Fire extinguisher is expired, have serviced or replaced | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(2) Hydraulic elevators Placed out of Service | Yes | Yes | Elevator has been decommissioned. |