Inspection
Inspection Details
Equipment ID
11409
11409
Inspection Date
9/19/2019
9/19/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
f0fa8d39-6570-4b42-a999-c78478edb39e
f0fa8d39-6570-4b42-a999-c78478edb39e
Location
IBM- Bldg 306
325 JAMES S MCDONNELL BLVD, HAZELWOOD, MO
Phone: (314) 234-6282
325 JAMES S MCDONNELL BLVD, HAZELWOOD, MO
Phone: (314) 234-6282
Owner
Attn: John Roberts
IBM- St. Louis
325 JAMES S MCDONNELL BLVD, HAZELWOOD, MO 63042
Phone: (314) 252-6228
Email: john.roberts@am.jll.com
IBM- St. Louis
325 JAMES S MCDONNELL BLVD, HAZELWOOD, MO 63042
Phone: (314) 252-6228
Email: john.roberts@am.jll.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(B) | No | No | Starting key switch needs to be replaced. | 2/2/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(G) | No | No | Need to do step indexing. | 2/2/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(B) | No | No | Key switch needs to be replaced. | 2/2/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | No | No | Cracks in left handrail at ends of bubble, needs to be replaced | 2/2/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(A) | Yes | Yes | Brake torque failed testing. Red tagged, re-inspection required | 7/21/2022 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | A copy of the MCP shall be kept in the machine room | 2/2/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | No | No | Cracks in left handrail at ends of bubble, needs to be replaced | 2/2/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | A copy of the MCP shall be kept in the machine room. | 2/2/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | No | No | Observed crack in right handrail, replace. | 4/1/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | Provide a maintenance control program | 4/1/2026 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post current state certificate in machine room | 4/1/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | Yes | No | Replace cracked and bubbling handrail. Repeat violation, re-inspection required. | 4/1/2026 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | A current MO State operating certificate shall be posted near the equipment, in a non-combustible frame with a clear protective vision plate over it. | 4/1/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | Compliant/required documentation shall be kept in equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log testing logs, etc. Missing MCP for 2022, 2023, & 2024. | 4/1/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Clean lower pit pan. Oil pads soaked with oil. | 4/1/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | Yes | No | Replace Left Handrail. Cracked and surface bubbling. CITED MULTIPLE YEARS:2025,2023, 2022 | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. |