Inspection
Inspection Details
Equipment ID
80
80
Inspection Date
9/30/2019
9/30/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Relief Valve Pressure
Na
Na
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
56c02f6a-c792-4566-8fc7-86f955f6fc1a
56c02f6a-c792-4566-8fc7-86f955f6fc1a
Location
St. Francis Hospital
2016 S MAIN ST, MARYVILLE, MO
Phone: (660) 562-2600
2016 S MAIN ST, MARYVILLE, MO
Phone: (660) 562-2600
Owner
St. Francis Hospital
2016 S MAIN ST, MARYVILLE, MO 64468-2655
2016 S MAIN ST, MARYVILLE, MO 64468-2655
Billing
Attn: St. Francis Hospital
2016 S MAIN ST, MARYVILLE, MO 64468-2655
2016 S MAIN ST, MARYVILLE, MO 64468-2655
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not operate | 9/30/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | Provide lighting in machine room. Existing feed for machine lights has no electrical power | 2/22/2021 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | Label machine room equipment with identification that corresponds to identification inside the elevator and the car crosshead. | 11/16/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Identify inside of hoistway doors with a numeral corresponding to landing floor. | 11/16/2021 | ||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Perform emergency standby operation with an inspector present. | 8/24/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Provide "Elevator Emergency Power" signal at the lobby of the designated landing. | 9/8/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not operate | 11/21/2023 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 (Re-Inspection) | x | Replace pit sprinkler head with sidewall sprinkler head located within 24 inches of pit floor | 11/21/2023 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | x | Test emergency power operation with inspector present | 11/21/2023 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | REPAIR PIT LIGHTING | 10/21/2024 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 2.13.4.2.3 | x | FRONT DOOR TORQUE IS >30lbs | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.5 - Normal terminal stopping device | 2.26.2 | x | DOWN LIMIT DID NOT WORK |