A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
Yes
|
No
|
The car door restrictor device has been removed to restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Provide a proper restrictor device to comply with code and passenger safety.
|
10/4/2018
|
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
Yes
|
No
|
The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required.
|
11/6/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
No
|
No
|
Need to replace 2 top left counterweight guide rollers
|
10/7/2025
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
Yes
|
No
|
Hoist ropes are at minimum allowable diameter and shall be replaced within 60 days. Alteration permit and inspection required. Re-inspection required
|
12/13/2024
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
No
|
No
|
Pit needs to be cleaned
|
10/7/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Provide & install test tag permanently marked with test data on all appropriate equipment. Re-inspection required
|
12/13/2024
|
|
A17.1-2016 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
8.6.4.13.1(l)(Door Restrictor)
|
Yes
|
No
|
The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Re-inspection required
|
12/13/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
No
|
No
|
Replace 2 top left counterweight guide rollers
|
10/7/2025
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
Yes
|
No
|
Hoist ropes are at a minimum allowable diameter and shall be replaced within 60 days. Alteration permit and inspection required. Re-inspection required
|
10/7/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.7.2 Periodic Test Record (Test Tags)
|
No
|
No
|
Provide and install test tags permanently marked with test data on all appropriate equipment
|
10/7/2025
|