Inspection
Inspection Details
Equipment ID
15009
15009
Inspection Date
9/13/2019
9/13/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Dustin Arnett
Dustin Arnett
Relief Valve Pressure
Slide
8"
8"
Governor Rope Pull
30/400
30/400
Door Closing Force
21
21
External ID
2fa253a3-a436-4b0a-ab10-749a2b45bbe3
2fa253a3-a436-4b0a-ab10-749a2b45bbe3
Location
Grace Lofts
1324 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 588-1170
1324 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 588-1170
Owner
Attn: Grace Lofts
McGowan Brothers
1324 WASHINGTON AVE, SAINT LOUIS, MO 63103-1938
McGowan Brothers
1324 WASHINGTON AVE, SAINT LOUIS, MO 63103-1938
Billing
Attn: McGowan Brothers
Jamie Fite
1314 WASHINGTON AVE STE 300, SAINT LOUIS, MO 63103-1919
Jamie Fite
1314 WASHINGTON AVE STE 300, SAINT LOUIS, MO 63103-1919
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | x | The car door restrictor shall work. | 1/10/2020 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency lighting shall work. | 1/10/2020 | |
A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | Independent service does not keep the doors open. | 1/10/2020 | ||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | x | x | Phase 2 fire service does not work. Phase 2 fire service shall be repaired and retested. | 1/10/2020 |
A17.1-1996 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 1002.3f | x | Repair the broken conduit on the car buffer switch. | 1/10/2020 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)2 | The car ceiling is about to fall down. Take corrective action to properly repair the car ceiling. | 9/14/2020 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Car & hoistway doors need to be adjusted for proper alignment and operation. | 8/12/2021 | |
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/16/2022 | ||
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Emergency light inside car does not work. | 10/16/2023 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 10/16/2023 | |
A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | x | Hoistway ropes are rouged and nearing the minimal allowable diameter and meet the criteria for replacement. | 10/16/2023 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | x | The roller guide on the front left side of the car top while facing the hall doors needs to be replaced. |